PreCooll utilizes the natural principle of water evaporation to create a
cooling effect. The system is installed around air-cooled chillers to precool the ambient air before it enters the condenser.
How It Works:
Hot ambient air approaches the cooling system, Water is distributed over the Oxyvap® pads, Air passes through the wet pads, causing water evaporation, Evaporation absorbs heat, cooling the air by up to 25°C, Cooled air enters the condenser, improving efficiency
The DAMAC EDGNEX data center in Riyadh represents a critical infrastructure investment supporting Saudi Arabia's Vision 2030 digital transformation goals. The facility operates in extreme desert conditions, requiring innovative cooling solutions.
Total Cooling Capacity: 5,280 kW
Chiller Configuration: 16 units with PreCooll
Design Ambient Temperature: 48°C
PreCooll Surface Area: 1,440 m²
Aquamizers: 32 units (2 per chiller)
Parameter | Without PreCooll | With PreCooll | Improvement |
Energy Consumption | 100% | 65% | 35% |
Peak Power Demand | 1,850 kW | 1,200 kW | 650 kW |
Annual CO Reduction | - | - | 1,650 tons |
ROI Period | - | - | 1.8 years |
Actual temperature readings from the DAMAC EDGNEX data center in Riyadh demonstrate significant cooling performance from the PreCooll system. Measurements were taken on June 1, 2022 during commissioning.
Number of chillers: 16
Number of Aquamizers: 32 (2 per chiller)
Each chiller includes: 2 Wet Walls + 2 Aquamizers
Metric | Value |
Morning Ambient Temperature (Chillers 1-8) | 40.2°C |
Afternoon Ambient Temperature (Chillers 11-18) | 42.8°C |
Average Supply Temperature After Wet Wall | 21.0°C |
Average Temperature Reduction | 20.5°C |
Temperature Reduction Range | 18.3°C - 22.2°C |
Estimated Energy Savings | 35% |