DAMAC Edgnex Data Center – Riyadh

PreCooll utilizes the natural principle of water evaporation to create a

cooling effect. The system is installed around air-cooled chillers to precool the ambient air before it enters the condenser.

How It Works:

Hot ambient air approaches the cooling system, Water is distributed over the Oxyvap® pads, Air passes through the wet pads, causing water evaporation, Evaporation absorbs heat, cooling the air by up to 25°C, Cooled air enters the condenser, improving efficiency

DAMAC Edgnex Data Center – RiyadhDAMAC Edgnex Data Center – Riyadh

Project Overview

The DAMAC EDGNEX data center in Riyadh represents a critical infrastructure investment supporting Saudi Arabia's Vision 2030 digital transformation goals. The facility operates in extreme desert conditions, requiring innovative cooling solutions.

Technical Specifications:

  • Total Cooling Capacity: 5,280 kW

  • Chiller Configuration: 16 units with PreCooll

  • Design Ambient Temperature: 48°C

  • PreCooll Surface Area: 1,440 m²

  • Aquamizers: 32 units (2 per chiller)

Performance Analysis:

Parameter

Without PreCooll

With PreCooll

Improvement

Energy Consumption

100%

65%

35%

Peak Power Demand

1,850 kW

1,200 kW

650 kW

Annual CO Reduction

-

-

1,650 tons

ROI Period

-

-

1.8 years

Temperature Reduction Analysis:

Actual temperature readings from the DAMAC EDGNEX data center in Riyadh demonstrate significant cooling performance from the PreCooll system. Measurements were taken on June 1, 2022 during commissioning.

3.png

System Configuration:

  • Number of chillers: 16

  • Number of Aquamizers: 32 (2 per chiller)

  • Each chiller includes: 2 Wet Walls + 2 Aquamizers

Key Performance Metrics:

Metric

Value

Morning Ambient Temperature (Chillers 1-8)

40.2°C

Afternoon Ambient Temperature (Chillers 11-18)

42.8°C

Average Supply Temperature After Wet Wall

21.0°C

Average Temperature Reduction

20.5°C

Temperature Reduction Range

18.3°C - 22.2°C

Estimated Energy Savings

35%